    Cooling of gas turbines inlet air through aquifer thermal energy storage

    , Article 2006 ASME Power Conference, Atlanta, GA, 2 May 2006 through 4 May 2006 ; Volume 2006 , 2006 ; 0791837769 (ISBN); 9780791837764 (ISBN) Bahadori, M. N ; Behafarid, F ; Sharif University of Technology
    2006
    Abstract
    The power output of gas turbines reduces greatly with the increase of inlet air temperature. Aquifer thermal energy storage (ATES) is employed for cooling of the inlet air of a gas turbine. Water from a confined aquifer is cooled in winter, and is injected back into the aquifer. The stored chilled water is withdrawn in summer to cool the gas turbine inlet air. The heated water is then injected back into the aquifer. A 20 MW Hitachi gas turbine, along with a two-well aquifer were considered for analysis. It was shown that the minimum power output of the gas turbine on the warmest day of the year could be raised from 16.30 to 20.05 MW, and the mean annual power output could be increased from... 

    Performance evaluation of a gas turbine operating noncontinuously with its inlet air cooled through an aquifer thermal energy storage

    , Article Journal of Energy Resources Technology, Transactions of the ASME ; Volume 129, Issue 2 , 2007 , Pages 117-124 ; 01950738 (ISSN) Behafarid, F ; Bahadori, M. N ; Sharif University of Technology
    2007
    Abstract
    The power output of gas turbines (GT) reduces greatly with the increase of the inlet air temperature. This is a serious problem because gas turbines have been used traditionally to provide electricity during the peak power demands, and the peak power demands in many areas occur on summer afternoons. An aquifer thermal energy storage (ATES) was employed for cooling of the inlet air of the GT. Water from a confined aquifer was cooled in winter and was injected back into the aquifer. The stored chilled water was withdrawn in summer to cool the GT inlet air. The heated water was then injected back into the aquifer. A 20 MW GT power plant with 6 and 12 h of operation per day, along with a...