    A novel hybrid islanding detection method for inverter-based DGs using SFS and rOCOF

    , Article IEEE Transactions on Power Delivery ; Volume 32, Issue 5 , 2017 , Pages 2162-2170 ; 08858977 (ISSN) Khodaparastan, M ; Vahedi, H ; Khazaeli, F ; Oraee, H ; Sharif University of Technology
    Abstract
    This paper is aimed at proposing a new hybrid method for the islanding detection of distributed-generation (DG) units. Hybrid method operation is based on the combination of an active and a passive method, for which the optimized Sandia frequency shift (SFS) method is used as the selected active method, and rate of change of frequency relay (ROCOF) is used as the passive method. In order to demonstrate the effectiveness of the proposed technique on islanding detection, several simulation studies based on IEEE 1547 and UL1741 anti-islanding test requirements are carried out. The evaluation of simulation results reveals that the control system, based on the proposed hybrid algorithm, meets the... 

    Multivariable control strategy for autonomous operation of a converter-based distributed generation system

    , Article 2011 IEEE/PES Power Systems Conference and Exposition, PSCE 2011, 20 March 2011 through 23 March 2011, Phoenix, AZ ; March , 2011 , Page(s): 1 - 8 ; 9781612847870 (ISBN) Nejati, A ; Nobakhti, A ; Karimi, H ; Sharif University of Technology
    2011
    Abstract
    This paper presents a control strategy for the autonomous (islanded) operation of a distributed generation (DG) unit. The DG unit supplies a balanced load through a voitage-sourced converter (VSC). To maintain the autonomous operation in the islanded mode, the DG unit should provide its dedicated load with a sinusoidal voltage with a constant magnitude and a constant frequency. The dynamic model of the islanded DG system is represented by a set of nonlinear equations. Since the objective is to regulate voltage and frequency of the islanded DG about their rated values, the nonlinear model is linearized about the operating point. The obtained linearized model represents a multivariable LTI... 

    Robust decentralized control for islanded operation of two radially connected DG systems

    , Article 2010 IEEE International Symposium on Industrial Electronics, ISIE 2010, Bari, 4 July 2010 through 7 July 2010 ; July , 2010 , Pages 2272-2277 ; 9781424463916 (ISBN) Moradi, R ; Karimi, H ; Karimi Ghartemani, M ; The Institute of Electrical and Electronics Engineers (IEEE); IEEE Industrial Electronics Society (IES); IEEE Control Systems Society (CSS); Society of Instrument and Control Engineers (SICE-Japan); Politecnico di Bari ; Sharif University of Technology
    2010
    Abstract
    A decentralized servomechanism controller for islanded (autonomous) operation of radial connection of two distributed generation (DG) units is proposed in this paper. Each DG unit utilizes a voltage-sourced converter (VSC) for interface to its dedicated load. The DG units and the loads are to operate in the islanded mode of operation. Each DG unit regulates the voltage of its dedicated load in a decentralized manner. In this paper, it is first shown that the radial connection of two DG units in the islanded mode constitutes an interconnected composite system consisting of two subsystems. Moreover, the paper shows that the overall islanded system can be controlled by the local controllers,... 

    Decentralized control of parallel connection of two distributed generation units

    , Article 35th Annual Conference of the IEEE Industrial Electronics Society, IECON 2009, Porto, 3 November 2009 through 5 November 2009 ; 2009 , Pages 358-362 Bahrani, B ; Karimi, H ; Iravani, R ; Sharif University of Technology
    Abstract
    This paper presents a decentralized control strategy for the autonomous (islanded) operation of parallel connection of two distributed generation (DG) units. The DG units are electronically interfaced to the host grid at the same point of common coupling (PCC), where the local load is also supplied. In the grid-connected mode, the voltage-sourced converter (VSC) of each DG unit controls the exchange of real and reactive power components with the host grid, based on the conventional dq-current control strategy. In the islanded mode, one of the DG units provides voltage and frequency control for the island, and the other DG unit continues to operate with the pre-islanding dq-current control...