    A Framework for Seismic Risk Assessment of Electrical Substation Equipment with Reliability and Endurance Time Methods

    , M.Sc. Thesis Sharif University of Technology Ghahremani Baghmisheh, Amir (Author) ; Esmaeil Purestekanchi, Homayoon (Supervisor)
    Abstract
    Influences of dynmic interaction between substation equipment on responses and fragility are studied. Proposing a framework for seismic risk analysis of substation equipment using reliability and endurance time methods is another aim of this project. Risk, in this contex, means the probability of exceeding monetary loss. Three dimensional models of four vulnerable types of equipment including surge arrester, current transformer, circuit breaker and disconnect switch are developed and verified. Six different systems of equipment connected through rigid bus bars comprising of two, three and four equipment are considered. Fragility curves are developed for equipment in both unconnected and... 

    Seismic Performance Evaluation of HV Circuit Breakers in Transmission Substations and Application of Base Isolation to Improve their Behavior

    , M.Sc. Thesis Sharif University of Technology Zare Feizabadi, Ali (Author) ; Bakhshi, Ali (Supervisor)
    Abstract
    The main goal of this study is to evaluate the seismic performance of HV circuit breakers of power substations and optimize their seismic behavior using base isolation systems. Iran is in a region with high seismicity and has experienced severe earthquakes in recent decades that have resulted in serious damages to critical infrastructures. These include power substations that are important during and even after an earthquake in providing electricity for homes, industries, amenities, emergency facilities, public transportation and more. The seismic performance of HV circuit breakers, which is an important equipment for power substations, has not been satisfactory in past earthquakes and has... 

    Fragility and Risk Analysis of Electrical Substation Equipment Using Reliability and Endurance Time Methods

    , M.Sc. Thesis Sharif University of Technology Delaviz Bonab, Arman (Author) ; Esmail Pourestekanchi, Homayoon (Supervisor)
    Abstract
    Electrical substations and its vital components such as switchgears, have experienced severe damage during recent earthquakes, followed by widespread blackouts around the world. To improve the seismic resiliency of power grids and use probabilistic decision-making frameworks, comprehensive fragility data for the different equipment is needed. The purpose of this study is to assess the vulnerability of equipment in substations and to develop fragility curves for this equipment. For this purpose, four main equipment of switchgear, namely circuit breaker, disconnect switch, current transformer and surge arrester, have been modeled in three dimensions and verified. After examining the different...