    A new algorithm for optimal measurement placement, observability analysis and harmonic state estimation in power systems

    , Article PEDSTC 2013 - 4th Annual International Power Electronics, Drive Systems and Technologies Conference ; 2013 , Pages 518-523 ; 9781467344845 (ISBN) Rad, M. S ; Mokhtari, H ; Karimi, H ; Sharif University of Technology
    2013
    Abstract
    Harmonic State Estimation (HSE) is a technique for identifying harmonic distributions in power systems with limited measurements. The main problem in HSE is the optimal placement of measurement meters such that the estimation error is minimized, while making the system fully observable. The second issue is the HSE method. This method must be accurate and fast enough in order to have an accurate HSE. This paper presents a new algorithm that uses minimum variance criterion (MVC) and a sequential method for optimal meters placement, SVD method for observability analysis and finally WLS method for harmonic estimation. The proposed method minimizes the number of measurement devices and the error... 

    An optimal measurement placement method for power system harmonic state estimation

    , Article EPE 2012 - Proceedings of the 2012 International Conference and Exposition on Electrical and Power Engineering ; 2012 , Pages 271-275 ; 9781467350013 (ISBN) Rad, M. S ; Mokhtari, H ; Karimi, H ; Sharif University of Technology
    2012
    Abstract
    Harmonic state estimation (HSE) method has been used to locate harmonic sources and estimate harmonic distribution in power systems with limited number of harmonic meters. This paper focuses on a new technique for optimal placement of measurement devices and observability analysis for power systems harmonic state estimation. The proposed method optimizes the number of measurements and minimizes the error of estimation at the same time. The method is tested on the IEEE 14-bus power system to show its precision