    Detection and Classification of Partial Discharges in High Voltage DC

    , M.Sc. Thesis Sharif University of Technology Rahimi, Mohammad Reza (Author) ; Vakilian, Mehdi (Supervisor)
    Abstract
    In past decades, the measurement of partial discharges (PDs) in high voltage equipments, was appreciated as one of the most efficient methods for evaluation of the equipment insulation condition. Generators, transformers, cables and transmission lines are especially checked to detect the presence of any partial discharge.
    In AC high voltage systems, the measurement method is well established and known. The Phase resolved method is used to determine the partial discharge signals. These methods have been used for many years and their success in differentiating the various sources of partial discharge have proven. Although phase resolved method works on AC; due to lack of frequency... 

    DC partial discharge characteristics for corona, surface and void discharges

    , Article Proceedings of the IEEE International Conference on Properties and Applications of Dielectric Materials, 19 July 2015 through 22 July 2015 ; Volume 2015-October , July , 2015 , Pages 260-263 ; 9781479989034 (ISBN) Rahimi, M. R ; Javadinezhad, R ; Vakilian, M ; Sharif University of Technology
    Institute of Electrical and Electronics Engineers Inc  2015
    Abstract
    Measurement of partial discharges (PDs) current pulses is found to be one of the most efficient methods to evaluate the high voltage electrical equipment insulation condition. Generators, transformers, cables and transmission lines are especially tested for the presence of PDs. In AC, the solution is well known. Phase-resolved method can be used to detect and determine partial discharge activities. Although phase-resolved method works well under AC voltage; due to lack of a cyclic variation in DC voltage and current this cannot be used when studying partial discharges in DC voltage systems. Therefore, other methods are employed to interpret the partial discharge in DC. For this purpose, the... 

    Data mining on partial discharge signals of power transformer's defect models

    , Article 2010 45th International Universities' Power Engineering Conference, UPEC 2010, Cardiff, 31 August 2010 through 3 September 2010 ; 2010 ; 9780956557025 (ISBN) Darabad, V. P ; Vakilian, M ; Sharif University of Technology
    2010
    Abstract
    Partial discharge (PD) is a common phenomenon which occurs in insulation of high voltage equipments, such as; transformers and has a damaging effect on the insulation. If data mining techniques be used to find specifications and features of different types of partial discharges in power transformers, one can monitor the insulation condition of such equipment online and continuously. Those results can be employed to develop preventive measures more exactly and consequently the maintenance would require less time and cost for electric utility and improve the life time expectancy of the transformers. In this paper experiments are set up to create models for some types of PD that occurs in Power... 

    An efficient diagnosis method for data mining on single PD pulses of transformer insulation defect models

    , Article IEEE Transactions on Dielectrics and Electrical Insulation ; Volume 20, Issue 6 , 2013 , Pages 2061-2072 ; 10709878 (ISSN) Darabad, V. P ; Vakilian, M ; Phung, B. T ; Blackburn, T. R ; Sharif University of Technology
    Institute of Electrical and Electronics Engineers Inc  2013
    Abstract
    Reviewing the various Partial Discharges (PD data mining researches which have been reported so far, this study compares the performance of different feature spaces and different classifiers employed for PD classification in insulation condition monitoring of power transformers. In this process, first a knowledge basis is developed through construction of 4 different types of PD models in the high voltage laboratory. Background noise is considered as one class in this knowledge basis. The high frequency time domain current signals of high voltage equipment are captured over one power frequency cycle. The single PD activities within this captured signal are extracted by application of a...