    HTS transformer windings design using distributive ratios for minimization of short circuit forces

    , Article Journal of Superconductivity and Novel Magnetism ; 2018 ; 15571939 (ISSN) Moradnouri, A ; Vakilian, M ; Hekmati, A ; Fardmanesh, M ; Sharif University of Technology
    Springer New York LLC  2018
    Abstract
    High-temperature superconducting (HTS) transformers have a promising feature in reduction of total weight, total size, and the losses of large-scale distribution transformers. However, the lower leakage reactance of HTS transformers results in a higher short-circuit fault currents and electromagnetic forces. Therefore, optimization of short-circuit electromagnetic forces is one of the crucial aspects in the design of HTS transformers. In this paper, a novel analytical method is proposed for determination of optimum distributive ratios resulting in minimization of these forces for asymmetrical multi-segment windings of an HTS transformer. Employing these distributive ratios, radial and axial... 

    HTS transformer windings design using distributive ratios for minimization of short circuit forces

    , Article Journal of Superconductivity and Novel Magnetism ; Volume 32, Issue 2 , 2019 , Pages 151-158 ; 15571939 (ISSN) Moradnouri, A ; Vakilian, M ; Hekmati, A ; Fardmanesh, M ; Sharif University of Technology
    Springer New York LLC  2019
    Abstract
    High-temperature superconducting (HTS) transformers have a promising feature in reduction of total weight, total size, and the losses of large-scale distribution transformers. However, the lower leakage reactance of HTS transformers results in a higher short-circuit fault currents and electromagnetic forces. Therefore, optimization of short-circuit electromagnetic forces is one of the crucial aspects in the design of HTS transformers. In this paper, a novel analytical method is proposed for determination of optimum distributive ratios resulting in minimization of these forces for asymmetrical multi-segment windings of an HTS transformer. Employing these distributive ratios, radial and axial... 

    HTS transformers leakage flux and short circuit force mitigation through optimal design of auxiliary windings

    , Article Cryogenics ; Volume 110 , September , 2020 Moradnouri, A ; Vakilian, M ; Hekmati, A ; Fardmanesh, M ; Sharif University of Technology
    Elsevier Ltd  2020
    Abstract
    Mitigation and control of leakage fluxes and short circuit forces needs much more attention, for a high-temperature superconducting (HTS) transformer, than for a conventional one. Different methods such as the application of auxiliary windings, multi-segment winding, and flux diverter have been presented in the literatures for leakage magnetic field reduction in HTS transformers. In this paper, for the first time, optimal design of auxiliary windings has been performed for a 132/13.8 kV, 50 MVA three phase core type HTS transformer. Genetic algorithm (GA) has been used for the optimization process. Induced current in auxiliary windings which is inversely proportional to the leakage fluxes... 

    Optimal design of flux diverter using genetic algorithm for axial short circuit force reduction in HTS transformers

    , Article IEEE Transactions on Applied Superconductivity ; Volume 30, Issue 1 , January , 2020 Moradnouri, A ; Vakilian, M ; Hekmati, A ; Fardmanesh, M ; Sharif University of Technology
    Institute of Electrical and Electronics Engineers Inc  2020
    Abstract
    The appealing advantages of high-temperature superconducting (HTS) power transformers over conventional ones have attracted transformer manufacturing companies, power companies, research institutes, and universities worldwide to conduct research and development in this field. Unfortunately, HTS transformers are more vulnerable to mechanical stresses than conventional transformers. The results of the interaction between current carrying windings and leakage magnetic fluxes are the electromagnetic forces, which act on transformer windings. Under short circuit events, these forces are remarkable, and, therefore, catastrophic failure of transformer may arise. Flux-diverter applications have been...