    DC partial discharge characteristics for corona, surface and void discharges

    , Article Proceedings of the IEEE International Conference on Properties and Applications of Dielectric Materials, 19 July 2015 through 22 July 2015 ; Volume 2015-October , July , 2015 , Pages 260-263 ; 9781479989034 (ISBN) Rahimi, M. R ; Javadinezhad, R ; Vakilian, M ; Sharif University of Technology
    Institute of Electrical and Electronics Engineers Inc  2015
    Abstract
    Measurement of partial discharges (PDs) current pulses is found to be one of the most efficient methods to evaluate the high voltage electrical equipment insulation condition. Generators, transformers, cables and transmission lines are especially tested for the presence of PDs. In AC, the solution is well known. Phase-resolved method can be used to detect and determine partial discharge activities. Although phase-resolved method works well under AC voltage; due to lack of a cyclic variation in DC voltage and current this cannot be used when studying partial discharges in DC voltage systems. Therefore, other methods are employed to interpret the partial discharge in DC. For this purpose, the...