Loading...
Search for: shunt--electrical
0.009 seconds

    Electric arc furnace power quality improvement using shunt active filter and series inductor

    , Article IEEE TENCON 2004 - 2004 IEEE Region 10 Conference: Analog and Digital Techniques in Electrical Engineering, Chiang Mai, 21 November 2004 through 24 November 2004 ; Volume D , 2004 , Pages D105-D108 Esfandiari, A ; Parniani, M ; IEEE Region 10 ; Sharif University of Technology
    2004
    Abstract
    This paper presents an investigation of power quality problems arising from electric arc furnace (EAF) operation, and the required compensating system capabilities. It also proposes a compensation system using a shunt active filter and a series inductor. A shunt active filter compensates for the reactive power and the current harmonics of the highly varying load. Reference signals for the compensation logic are obtained from the instantaneous current vector components on a rotating reference frame. Due to noninteger harmonics on voltages at the point of common coupling, conventional methods for the inverter dc bus voltage regulation fail to perform properly. Hence, a new method is introduced...