    Geometric-based fault diagnosis in a grid-connected inverter

    , Article Proceedings of the IEEE Conference on Decision and Control, 17 December 2018 through 19 December 2018 ; Volume 2018-December , 2019 , Pages 3421-3426 ; 07431546 (ISSN); 9781538613955 (ISBN) Mashreghi, A ; Namvar, M ; Sharif University of Technology
    Institute of Electrical and Electronics Engineers Inc  2019
    Abstract
    This paper presents a nonlinear geometric approach to fault detection and isolation (FDI) in grid-connected inverters. Faults are considered in inverter switches as well as in grid voltage and source current sensors. The FDI system is not sensitive to load variations or grid transients. No assumptions on balanced, zero-sum or sinusoidal form of voltages or currents are made. The resulting residual converges to zero in no-fault condition such that no threshold adjustment is needed. Simulations demonstrate performance of the proposed FDI system in presence of unknown disturbance. © 2018 IEEE  

    A geometric approach to fault detection and isolation in a grid-connected inverter

    , Article IEEE Transactions on Control Systems Technology ; Volume 29, Issue 6 , 2021 , Pages 2622-2629 ; 10636536 (ISSN) Mashreghi, A ; Namvar, M ; Sharif University of Technology
    Institute of Electrical and Electronics Engineers Inc  2021
    Abstract
    We present a nonlinear geometric approach to fault detection and isolation (FDI) in a grid-connected inverter system. Open-switch faults in inverter power transistors together with faults in grid voltages and source current sensors are detected and isolated in the presence of disturbance. The detection process is based on dynamic model of an inverter, including a dc-bus capacitor and an output $RL$ filter. The proposed FDI system does not rely on balanced or zero-sum conditions in the grid point and is functional under nonsinusoidal voltages and currents. © 1993-2012 IEEE  

    A geometric approach to fault detection and isolation in a grid-connected inverter

    , Article IEEE Transactions on Control Systems Technology ; November , 2020 , Pages: 1-8 Mashreghi, A ; Namvar, M ; Sharif University of Technology
    Institute of Electrical and Electronics Engineers Inc  2020
    Abstract
    We present a nonlinear geometric approach to fault detection and isolation (FDI) in a grid-connected inverter system. Open-switch faults in inverter power transistors together with faults in grid voltages and source current sensors are detected and isolated in the presence of disturbance. The detection process is based on dynamic model of an inverter, including a dc-bus capacitor and an output RL filter. The proposed FDI system does not rely on balanced or zero-sum conditions in the grid point and is functional under nonsinusoidal voltages and currents. IEEE