Loading...
Search for: ul1741-test
0.004 seconds

    Nondetection zone assessment of an active islanding detection method and its experimental evaluation

    , Article IEEE Transactions on Power Delivery ; Volume 26, Issue 2 , 2011 , Pages 517-525 ; 08858977 (ISSN) Bahrani, B ; Karimi, H ; Iravani, R ; Sharif University of Technology
    2011
    Abstract
    This paper analytically determines the nondetection zone (NDZ) of an active islanding detection method, and proposes a solution to obviate the NDZ. The method actively injects a negative-sequence current through the interface voltage-sourced converter (VSC) of a distributed generation (DG) unit, as a disturbance signal for islanding detection. The estimated magnitude of the corresponding negative-sequence voltage at the PCC is used as the islanding detection signal. In this paper, based on a laboratory test system, the performance of the islanding detection method under UL1741 anti-islanding test conditions is evaluated. Then, determining the NDZ of the method and proposing the...