Nondetection zone assessment of an active islanding detection method and its experimental evaluation
, Article IEEE Transactions on Power Delivery ; Volume 26, Issue 2 , 2011 , Pages 517-525 ; 08858977 (ISSN) ; Karimi, H ; Iravani, R ; Sharif University of Technology
2011
Abstract
This paper analytically determines the nondetection zone (NDZ) of an active islanding detection method, and proposes a solution to obviate the NDZ. The method actively injects a negative-sequence current through the interface voltage-sourced converter (VSC) of a distributed generation (DG) unit, as a disturbance signal for islanding detection. The estimated magnitude of the corresponding negative-sequence voltage at the PCC is used as the islanding detection signal. In this paper, based on a laboratory test system, the performance of the islanding detection method under UL1741 anti-islanding test conditions is evaluated. Then, determining the NDZ of the method and proposing the...