Standing phase angle reduction based on a wide area monitoring system using genetic algorithm

Nourizadeh, S ; Sharif University of Technology | 2010

788 Viewed
  1. Type of Document: Article
  2. DOI: 10.2202/1553-779X.2513
  3. Publisher: 2010
  4. Abstract:
  5. During power system restoration, it is necessary to check the phase angle between two buses before closing circuit breakers to connect a line between them. A novel approach for reducing large standing phase angle (SPA) based on Genetic Algorithm (GA) is presented in this paper. The proposed approach starts with a state estimation on Wide Area Monitoring System (WAMS) data measurements and considering power system operation and angular stability constraints, seeks an optimal control action scenario for reducing SPA. Since these constraints are evaluated based on WAMS data, the presented approach is considerably high speed and accurate. As an optimization problem, objective function of the proposed approach is to minimize variation from the current state of the power system. Simulation results on the IEEE 118 bus test system clearly show efficiency of the approach. Copyright
  6. Keywords:
  7. Genetic Algorithm (GA) ; Standing Phase Angle (SPA) ; Power system optimization ; Power system restoration ; Standing phase angle ; Wide area monitoring system ; Wide Area Monitoring System (WAMS) ; Control system stability ; Genetic algorithms ; Mobile telecommunication systems ; Optimization ; Restoration ; State estimation ; Monitoring
  8. Source: International Journal of Emerging Electric Power Systems ; Volume 11, Issue 3 , Jul , 2010 ; 1553779X (ISSN)
  9. URL: https://www.degruyter.com/abstract/j/ijeeps.2010.11.3/ijeeps.2010.11.3.2513/ijeeps.2010.11.3.2513.xml